EMS integration
Furo builds on your asset's EMS: which data flows, which ways there are and what the EMS has to provide for it.
Furo does not build its own EMS. Control on site stays with your asset's energy management system or power plant controller; Furo computes in the cloud and tells it what the battery should do in the next quarter hour. For this to work, two things have to flow: the measurements from the site to Furo, and the schedule from Furo back to the battery. This connection is called an integration.
What flows to Furo
At least every 15 minutes one set of measurements from the site — many integrations deliver more often:
- the consumption of the property
- the PV generation
- state of charge and power of the battery
- the power at the grid connection point, i.e. what is currently imported from or exported to the grid
From these Furo computes the forecast for the next hours and optimizes the battery's operation on it.
What flows back
A schedule: for every quarter hour a setpoint for how strongly the battery charges or discharges, plus the limits that must not be exceeded. Furo always computes several hours ahead — so the result is a schedule, not just a single value for the moment.
The schedule goes specifically to the battery. Consumption and PV are only measured, not controlled.
If a partner markets your battery's free flexibility, Furo additionally reports to them how much power is free per quarter hour and builds the traded volumes into the schedule. Nothing changes for the connection at the site — the same measurements and the same schedule flow.
The difference between the connections
Which data flows is the same for every asset. What differs is only which way it flows — and above all, who opens the connection. That is exactly what decides what has to be approved at the site.