Furo Docs

CHP

How to include an existing combined heat and power plant in the analysis: which profile to upload, how the feed-in is remunerated and what the KWKG bonus is.

In the Upload step your Generation plants are listed on the left. The + below the list adds a combined heat and power plant (CHP) as well as a PV plant; the bin at the top of the box removes it again. If the site has no PV system, you still answer "On-site generation installed or planned?" with Yes under Basic Information, add the CHP here and remove the PV system with its bin. The analysis treats it as an existing plant: it does not size it and calculates no investment costs, but takes the profile you upload exactly as the plant was operated. One CHP per analysis.

The analysis always treats the CHP as feeding into the grid.

If a PV system is in the form too, the CHP box asks "Which plant has priority for charging and export?". The plant with priority counts first as battery charging, then as export; the other counts first as covering the load, the charging load of EV charging included. If only one plant has its own generation meter, it has priority. If both have one, you choose the priority by declaration. The choice is binding and can be changed at the earliest from the next calendar year (MiSpeL Annex 1, section 6.5). PV is preselected, as is market standard.

Which profile to upload

This depends on the load profile you entered under Load profile and on whether a PV system comes with it.

Your caseCHP generation profileCHP feed-in profilePV Feed-in ProfilePV Production Profile
Gross loadrequired——with PV: upload or simulate
Grid consumption, no PVrequiredrequired——
Grid consumption, PV only plannedrequiredrequired—upload or simulate
Grid consumption, existing PVrequired—required, as Total feed-in (PV + CHP)required (upload)
Grid consumption, existing PV, Feed-in metered separatelyrequiredrequiredrequiredupload or simulate
Grid consumption, existing PV, CHP Plannedrequired—requiredupload or simulate

You can enter grid consumption without a PV system too: choose Grid Consumption (Net) under "What type of load profile is available?", add the CHP here and remove the PV system.

With a gross load the self-supply is not yet deducted — the analysis splits the generation into self-supply and surplus itself. With grid consumption the self-supply is already deducted, so the feed-in comes on top. You need the generation profile in every case: without it the analysis can compute no CHP figure.

Beside an existing PV, you upload the feed-in your grid operator supplies for both plants together once, in the PV 1 box, as Total feed-in (PV + CHP), even with several existing PV systems. The analysis splits it using the measured generation profiles of both plants — which is why both are then required. If each plant has its own feed-in profile, click "Feed-in metered separately" below the total feed-in upload: you then upload only the PV's feed-in in the PV 1 box and the CHP's in the CHP box. Switching discards a feed-in already uploaded in the PV 1 box, because the file then has to contain something else.

With grid consumption you choose for the CHP and in the first PV box whether the plant is an Existing system or Planned; every further PV system takes the first box's type. At least one plant has to be running already: if the PV is Planned, the CHP is fixed to Existing system, and the other way round. If every plant is planned, your load profile is the total consumption: choose Total Consumption (Gross) under Load profile. A planned CHP is not in your load profile yet, so it needs its generation profile and no feed-in profile. With a gross load the CHP box does not ask the type, since there it makes no difference to the calculation.

The format is the same as for the other profiles: a CSV with timestamp and value, the values in kW or in kWh per interval — you pick the unit on upload as for the load profile. Resolution and calendar year are free, but the timestamps have to sit on the quarter-hour grid and cover your load profile's period. Nothing is scaled up: the rated power only feeds the suggested KWKG bonus and the plausibility check of the generation profile.

Marketing of CHP power

ModelWhat you enterWhat you get per kWh fed in
Direct marketing (spot price)—the spot price of the quarter hour, plus the KWKG bonus
EEG (direct marketing with market premium)reference value (anzulegender Wert) in €/kWhyour reference value, without a KWKG bonus

CHP power fed in via the battery earns no KWKG bonus (MiSpeL Annex 1, fn. 29), only the spot price. With CHP priority, CHP kWh count first as battery charging and lose the bonus; with PV priority, PV power counts first, and its share of the battery's feed-in keeps the market premium.

Every analysis plans a battery, and with a CHP and a battery the analysis follows the MiSpeL Abgrenzungsoption. It rules out commercial offtake by the grid operator, CHP power included (MiSpeL Annex 1, section 3.1.1). That is why there is no model for it. The same goes for an EEG-funded CHP: the Abgrenzungsoption rules out the fixed feed-in tariff, so it is billed only in direct marketing with the market premium.

The EEG market premium and the KWKG bonus are mutually exclusive: a plant funded under the EEG falls outside the KWKG (§ 1 (3)) — typically biogas, biomethane and wood-fired CHP. Pick this model and the bonus field stays in place but can no longer be filled in, and 0 is used. Having both would count the feed-in twice: once inside the reference value, which already contains the market value, and once beside it.

The KWKG bonus

The CHP box also asks for the Rated electrical power and the Year of commissioning. Enter both and the analysis fills the bonus in for you. Together they fix the rate: the power through the § 7 KWKG tier table, the year through the KWKG version the plant is paid under. The field stays overwritable — your approval notice is what counts.

§ 7 KWKG tiers the rate by power band, so the rate is a blended one across the rated power:

Power bandBonus
up to 50 kW8 ct/kWh
50 – 100 kW6 ct/kWh
100 – 250 kW5 ct/kWh
250 kW – 2 MW4.4 ct/kWh
above 2 MW3.1 ct/kWh commissioned up to 2020, 3.4 ct/kWh from 2021

A 400 kW plant therefore gets (50·8 + 50·6 + 150·5 + 150·4.4) / 400 = 5.28 ct/kWh — not 4.4. That is exactly what the field suggests.

What the commissioning year changes:

Year of commissioningWhat is suggested
before 20160 — the plant is paid under the version of its own year, and those entitlements have run out almost everywhere
from 2016the blended rate from the tier table
from 2020, new plant up to 50 kWa flat 16 ct/kWh instead of the tier table's 8 ct/kWh (§ 7 (3a)); a modernised plant earns the 8 ct/kWh, which you overwrite
from 2027the same rate, with a hint: the bonus applies only if the plant was approved or bindingly ordered by 31 Dec 2026 and goes into continuous operation within four years of that (§ 6 (1))

Once a generation profile is uploaded, the card estimates how many of the 30,000 subsidised full-load hours (§ 8 (1) KWKG; 60,000 up to 50 kW in continuous operation before 2020) the plant has already spent: from annual generation, rated power and commissioning year, each year capped under § 8 (4). Once the estimate reaches that number the field warns. It does not replace your approval notice — it knows nothing of downtime or a start part-way through a year.

The field works in €/kWh, the tier table is in ct/kWh. For the 400 kW plant you enter 0.0528, not 5.28.

At a spot price of zero or below the bonus lapses (§ 7 (5)). The analysis handles that itself, so enter the full rate.

The analysis does not model the annual cap under § 8 (4) KWKG: since 2021 a year earns at most 5,000 subsidised full-load hours, from 2023 4,000, from 2025 3,500, and then 200 fewer each year down to 2,500 from 2030. Only the hours estimate in the form applies it. For a heat-led CHP with more operating hours the bonus revenue shown is therefore too high.

What the results show

The CHP card shows annual generation, peak power, self-consumption rate, self-sufficiency, the generation-to-load ratio and the peak load reduction. In both self-sufficiency donuts — the one on the PV card and the one beside the energy flows — the CHP gets its own segment, which would otherwise disappear into the grid share.

The donut beside the energy flows shows how much the PV and the CHP cover with the battery, as the analysis books it under the MiSpeL Abgrenzungsoption. The PV and CHP cards show today's state without a battery instead. That is why the PV and CHP figures can differ between the donut and the cards.

In the Energy Flow Diagram the PV and the CHP share one On-site generation frame; the arrows to the battery, the grid and the load carry the sum of both plants. Clicking a value shows how much of it came from the PV and how much from the CHP. Without PV the CHP stands there alone.

In the Peak Shaving Peaks chart the net-load bar names both generators — the shaving the CHP does is in there and is no longer credited to the PV.

In the Load Distribution chart the CHP generation sits beside the PV generation as a purple area — with grid consumption only the feed-in, because the self-supply is already netted out of your load profile. In the Use of On-Site Generation donut beside the energy flows the CHP has its own segment for the load it covers itself; “Battery” and “Grid” hold both generators.

The PV figures stay strictly PV: PV self-consumption and PV peak reduction do not include the CHP's self-supply. The feed-in revenue, by contrast, does include the CHP export.

What the analysis cannot do today

  • The CHP is never curtailed, not even at a negative spot price. The battery works around a fixed profile.
  • Existing and planned PV together with a CHP are not possible yet.
  • The bonus on self-consumed electricity is missing. The field only acts on the kWh fed in. On self-consumption the bonus is paid only in special cases (plants up to 100 kW, supply within a customer installation, electricity-intensive companies, § 6 (3) KWKG); the analysis does not count it there, so the result is then on the cautious side.
  • One CHP per analysis, and only for sites in Germany — the analysis applies the bonus under the KWKG.
  • A CHP cannot be combined with the operator model.